|
SECTION
III: CONTROLS
Atmospheric
Monitoring Equipment & General Testing Protocol
Dangerous
concentrations of gases and vapors may exist
in a confined space and these hazards cannot
be seen and may not be smelled. Therefore, air
monitoring equipment is necessary to properly
test the space prior to entry.
There
are two (2) major types of direct reading atmospheric
testing equipment used, electronic gas detectors
and gas detector tubes. Direct reading instruments
are portable units which can be carried in hand
or worn on a belt. These devices may be subject
to cross‑sensitivity, which means that
more than one chemical can give the same or
similar response. Interfering chemicals may
give a positive or negative deflection from
the true atmospheric concentrations. Other factors,
which are discussed later in this section, may
have a direct influence on the proper use and
reliability of this equipment. Therefore, it
is very important that the individual performing
the tests be properly trained on the actual
use, maintenance, limitations, and proper selection
of the appropriate instrument.
Electrical
Gas Detection Monitors
Electrical
gas detection instruments are battery‑powered,
direct‑reading devices capable of providing
continuous monitoring of a permit space. Oxygen
monitors measure atmospheric concentrations
generally over a range of 0 to 25 percent oxygen
in air.
Combustible
gas monitors display concentrations in percent
of the LEL, some in percent by volume, and others
display both. However, most combustible gas
monitors display concentrations in percent of
the LEL. Instruments that measure in the percent
of the LEL are generally easier to use. For
example, the LEL of methane is 5 percent by
volume and the UEL is 15 percent by volume.
When the concentration in a space reaches 2.5
percent by volume, it is 50 percent of the LEL.
When the concentration reaches 5 percent by
volume, it is 100 percent of the LEL.
Toxic
gas monitors use specific electrochemical cells
to measure substances such as carbon monoxide,
hydrogen sulfide, chlorine, ammonia or other
toxic gases of interest. The instruments are
direct reading, available with either meters
or digital read‑outs and may also be equipped
with alarms. Some instruments are equipped with
a single sensor while others have multiple sensors
to simultaneously measure a variety of gases.
These devices are commonly referred to as 2‑in‑1,
3‑in1, 4‑in‑1 monitors.
It
is very important to select the instrument for
the specific applications(s) to be encountered.
Therefore, whenever specific contaminants have
been identified, substance specific detectors
should be used.
Special
consideration must also be given to the use
and interpretation of the results obtained from
electrical gas meters under certain circumstances.
The operator must be aware of situations which
could interfere with the collection of accurate
monitoring data. Instrument familiarization
by the operator is needed for accurate atmospheric
testing. A thorough understanding of the manufacturer's
written operating instructions is a major component
for the safe and effective use of the instrument.
Therefore, employees who use this equipment
must be trained on these operating instructions
and receive hands‑on training as well.
The operator should also be aware of the following
facts concerning electrical gas monitors:
1)
The instrument must be certified intrinsically
safe for use in Class1, Division1, Groups
A, B, C, and D hazardous locations.
2)
Some combustible gas meter sensors are wheatstone
bridge type sensors. This type of sensor can
be easily poisoned by silicone vapors, leaded
gasoline, sulfur compounds, and repeated exposure
to halogenated hydrocarbons. This desensitization
will cause erroneous low readings and appreciably
reduce the life expectancy of the sensor.
3)
The instrument selected must be specific to
the substances likely to be found.
4)
High relative humidity (90‑100%) may
cause a reduction in sensitivity and erratic
behavior including an inability to properly
calibrate the instrument.
5)
Sensors have a limited life span, for example,
oxygen sensors typically have a one year life
span. Exposure to corrosive substances such
as acid gases can significantly reduce sensors'
life expectancy.
6)
Erroneously low‑readings can result
from substances condensing in the sampling
line or sensors. Substances such as chlorine,
hydrogen sulfide, sulfur dioxide, and ammonia
are some of the substances which can be absorbed
into the sampling line. In drying ovens or
unusually hot locations, solvent vapors with
high boiling points may condense in the sampling
lines.
7)
Battery maintenance is very important. There
are basically three different types of batteries
currently used: nickel cadmium, alkaline,
or sealed lead‑acid. Each has advantages
and disadvantages which should be researched
with the manufacturer at the time of purchase.
8)
Make sure the instrument has remote sampling
capabilities.
9)
Calibration of Electronic Gas Detectors
Gas
detectors must be checked and calibrated each
day prior to use. The inspection should include
checking hoses, batteries, and any pumps the
equipment might have. The unit must also be
field tested using test gas cylinders containing
known amounts of the substance to be encountered.
Oxygen
meters should be calibrated in fresh air to
21%. They should also be tested to see if they
respond to changes by holding one's breath and
then breathing into the sensor. The sensor should
drop to approximately 16%.
If
the equipment does not calibrate properly, the
unit must be removed from service. Replace the
sensor or return the unit to the factory for
repair and/or laboratory recalibration.
Operators
should consult with the manufacturer's instructions
or calibration curves when sampling for gases
and vapors against which the instrument was
not calibrated.
Detector
Tubes/Pumps Method
Detector
tube pumps are portable instruments which use
a variety of detector tubes to measure the concentration
of a wide variety of substances. The operating
principle consists of drawing a known volume
of air through a detector tube designed to measure
the concentration of the substance of interest.
Detector
tubes are easy to use and provide a relatively
good idea of the concentration of a substance
within a space. The length of stain or degree
of color change corresponds to the relative
concentration of the substance tested. The tubes
are generally specific for the toxic substance
of concern. However, the accuracy can be affected
by cross‑sensitivity. Therefore, the results
must be interpreted in relation to the substances
in the space.
Limitation
for detector tubes include:
-
Tubes can not be interchanged with different
brands.
-
Tubes may lack specificity; cross-sensitivity
with other compounds is possible. Refer to
the manufacturer's manual for effects of interfering
substances.
-
Detector tubes give only instantaneous results
-
Tubes have a limited shelf-life (approximately
1-2 years). Refrigeration can extend their
shelf life. However, tubes exceeding their
expiration date should not be used.
-
Accuracy ranges vary with each detector tube
-
Tube accuracy is significantly affected by
cold temperatures. In cold temperatures, try
to keep the tubes in a pocket close to the
body to keep them warm.

Calibrations
and Maintenance:
Operators
are reminded to consult the manufacturer's instructions
for specific procedures for the calibration
and maintenance of the instrument.
General
recommendations when conducting atmospheric
testing:
1)
Use only monitoring instruments that have
been properly calibrated and maintained and
that are intrinsically safe.
2)
Only trained operators who are skilled and
knowledgeable with the use and limitations
of the instrument should do the testing.
3)
Check the area around the confined space opening
for any hazardous gas or vapor concentrations.
4)
Extreme care must be exercised when opening
any confined space that may contain an explosive
atmosphere. Some spaces may contain an atmosphere
too rich to burn. But when opening the space,
air entering will quickly change the atmosphere
to an explosive one. Sparks from removing
the hatch or cover could ignite the space.
Therefore, insert the test probe into a vent
hole when possible. If the manhole cover or
hatch has no vent opening, open the cover
just far enough to insert the probe into the
space. Spark‑proof tools must be used.
If unacceptable levels are obtained, it will
be necessary to purge and ventilate the space.
All levels and remote areas of the space need
to be tested. An extension device should be
used for this purpose. If a hazardous atmosphere
is detected, avoid having employees lean over
the opening or breathe the air coming out
of the space.
5)
Oxygen content is always tested first. Make
sure sufficient oxygen is available to support
the use of the combustible gas monitor. A
minimum of 16% oxygen is required for the
combustible has monitor to function properly.
The sampling protocol requires that combustible
gas levels in the confined space be checked
next. Flammable gases or vapors must not exceed
10% of the lower flammability limit (LFL).
6)
Toxic substances are measured next in parts
per million (ppm). Again, the equipment used
must be specific and sensitive to the substance
likely to be found in the space. Never use
a standard flammable gas monitor sensor to
test for a toxic substance. The results could
be deadly as the following example will show.
| Percentage
of LFL |
Hydrogen
Sulfide PPM |
| 100% |
43,000 |
| 10% |
4,300 |
| 5% |
2,150 |
| .7% |
300
IDLH |
| .02% |
10
PEL |
Hydrogen
sulfide is a common toxic gas encountered in
many permit space locations. Hydrogen sulfide
has an LFL of 4.3% or 43,000 ppm. The standard
requires maintaining an environment of less
than 10% of the LFL to avoid a potential explosion.
Hydrogen sulfide also has Permissible Exposure
Limit (PEL) of 10 ppm and an Immediate Dangerous
to Life and Health (IDLH) concentration of 300
ppm. Say, for example, the LFL is found to be
5%, though the testing indicates no explosive
hazard, it does indicate a level of approximately
2,150 ppm which exceeds the PEL and IDLH.
7)
Some toxic substances may not respond very
well to electrical gas sensors or detector
tubes so more specialized test equipment or
laboratory analysis may be necessary.
8)
Depending on their density, some gases are
heavier than air, others lighter, and some
gases are nearly the same weight as air. As
a result, gases and vapors will stratify within
a given confined space. Therefore, the only
safe way to test the atmosphere of a confined
space is to sample all levels (top, middle,
bottom) with properly calibrated equipment.
When monitoring for entries involving a descent
into atmospheres which may be stratified,
the atmospheric envelope should be tested
a distance of approximately four feet (1.22
meters) in the direction of travel and to
each side. If a sampling probe is used, the
entrant's rate of progress should be slowed
to accommodate the sampling speed and detector
response.
Ventilation
Once
a confined space has been determined to contain
or potentially contain a hazardous atmosphere,
steps must be taken to ventilate the space before
personnel are allowed to enter. Ventilation
can be accomplished by natural and mechanical
means for the general purpose of:
-
Controlling atmospheric contaminants
-
Prevention of fire and explosion hazards
-
Control of heat and humidity
Natural
Ventilation
Natural
ventilation is performed by removing roof and
side covers and allowing natural air currents
to remove gases and vapors. Natural ventilation
employs wind and thermal convection to dilute
any atmospheric hazard. However, the configuration
of some confined spaces and the unpredictability
of wind currents and thermal effects makes natural
ventilation unreliable as a primary control
method. When natural ventilation is insufficient
to achieve and maintain acceptable atmospheric
levels, mechanical ventilation is necessary.
Mechanical
Ventilation
Mechanical
ventilation typically refers to mechanical dilution
ventilation and local exhaust capture ventilation.
The applicability of each method is dependent
on the type of atmospheric hazard present, whether
the hazard is created by the contents in the
space, or created by an operation conducted
within the space. When alternative procedures
are used, mechanical dilution ventilation is
prerequisite.
Mechanical
Dilution Ventilation
This
method uses mechanical means (fans, blowers,
etc.) to provide uncontaminated air to a permit
space. This control measure places the permit
space in a positive pressure atmospheric condition.
If the amount of fresh air being supplied to
the space is sufficient, the concentrations
of toxic and flammable contaminants can be maintained
at acceptable levels. The acceptable dilution
ventilation method commonly used is to supply
clean air by explosion‑proof blowers located
far enough away from any source of contamination.
Air
should be blown into a space, which contains
a hazardous atmosphere. Remember that contaminants
are likely heavier or lighter than air. Blowing
air into a space will agitate and help evaporate
the contaminants and disperse them throughout
the space. A space under positive pressure will
eventually expel the contaminant through any
openings in the space. Theoretically, air blows
a distance of 30 diameter times farther than
it can be exhausted.
If
an actual or potential hazardous atmosphere
exists, then purging of the space is necessary.
Keep in mind that forced air ventilation must
be directed to ventilate the immediate area
where an employee will be or is working. However,
during the initial pre‑entry ventilation
procedure, the blowing duct outlet should be
positioned for uniform dilution and elimination
of any gas pockets as illustrated. Shown below
are examples of complete and incomplete ventilation
of manholes:
When
purging a space, an effective initial purging
duration must be determined. The following is
a list of instructions for determining purging
times using the nomographs (line charts) provided.
Instructions
1)
Test the confined space atmosphere to determine
the initial atmospheric conditions.
2)
Use the alignment chart to determine the minimum
purging time required by:
a)
placing the straight edge on the Confined
Space Volume (left scale);
b)
placing the other end of the straight edge
on the Blower Capacity (right scale);
c)
read the minimum required purging time from
the diagonal scale in minutes
d)
if two blowers are used, add the two capacities
and then proceed as outlined above.
3)
Note, the effective blower capacity is affected
by the number of bends and length of the hose.
As the length of hose and the number of bends
increases, the effective blower capacity will
decrease. The effective blower capacities listed
in the alignment charts are based on one to
two 90 degree bends and standard 15‑foot
blower hose.
4)
It is very important to remember that these
values are theoretical approximations with safety
margins included. The duration for purging a
space is dictated by not only the size and blower
capacity, but also by the configuration, number
of openings and the airborne contaminant. The
configuration of some confined spaces, for example
multi‑floor‑level spaces or baffled
spaces, restrict air flow and require additional
purging time. In some situations, adequate purging
and venting can only be achieved through permanently
installed ventilation ducts that will introduce
fresh air directly into the space. In light
of this, employers are encouraged to install
permanent ventilation ducts whenever possible.
Examples are shown in the following illustrations.
5)
Employers are further reminded that under no
circumstance should entry be allowed at the
end of the purging time until the atmosphere
is tested and shown to be within acceptable
levels. If unacceptable levels are obtained,
then it will be necessary to repeat the process.
6)
If forced air ventilation is necessary to control
any existing potential atmospheric hazards,
then the blower must remain in constant operation
for the duration of the permit space entry operation.
The
theoretical purging time can also be determined
using the ventilation calculations provided.
Alignment
Chart ‑ Side 1
Confined
Space VolumeEffective Blower Capacity
(Cubic Feet)(CFM)
VENTILATION
CALCULATIONS
1)
Determine the flow rate (Q) required to achieve
20 air changes per hour (ACH) in an underground
lift station 20 ft. high, 40 ft. long, and 20
ft. wide.
EQUATION
|
N = |
Q
x 60 |
N = Nos. of ACH |
|
VOL |
Q = Ventilation Flow Rate (CFM) |
|
|
60
= Constant (mins/hrs) |
|
20 ACH = |
Q
x 60 min/hr |
Vol = Space Volume (ft3) |
|
16,000
ft3 |
|
|
|
Answer:
N=20 |
|
|
|
| Q
= |
20
AC/hr x 16,000 ft3 |
Q
= ? |
|
60
mins/hrs |
Vol
= 20x40x20 = 16,000 ft.3 |
|
|
|
|
|
Answer:
Q= 5,333 ft3 /min |
2)
A permit-required confined space 20'x30'x10'
in size is found to have an initial concentration
of 250 parts per million (ppm) of carbon monoxide.
How long will it take to lower the concentration
to 50 ppm using a portable ventilation unit
with a flow rate of 1000 cfm?
EQUATION
|
t = |
-2.303
(Vol/Q) x log (C2/C1) |
|
| t
= |
2.303
x (6,000 ft3/1,000 ft3/min)
x log (50ppm/250 ppm) |
|
| Answer: |
t=9.6
mins. |
|
|
|
|
|
|
|
| t
= 9.6 mins. |
Vol
= 20'x30'x10' = 6,000 ft3 |
| t
= time (minutes) |
C1=
250 ppm |
| Vol
= space volume (ft3) |
C2
= 50 ppm |
| Q
= ventilation flow rate (CFM) |
Q
= 1,000 cfm |
| C1
= initial contaminant concentration (ppm) |
-2.303
= constant |
| C2
= final contaminant concentration (ppm) |
t
= ? |
|
|
|
3)
What will be the concentration of hydrogen sulfide
(H2S) after 20 minutes of purging a cylindrical
tank (40' high with a 10' diameter)? The initial
concentration is 200 ppm and the ventilation
rate is 800 cfm.
EQUATION
C2 = C1 x e (-Qt/Vol)
| C1
= initial contaminant concentration |
C1
= 200 ppm |
| C2
= final contaminant concentration |
C2
= ? |
| e
= inverse natural log |
Q
= 800 fpm |
| Q
= ventilation flow rate (CFM) |
t
= time (minutes) |
|
t = 20 mins. |
vol
= space volume (ft3) = 40' x
[TT x D2]/4]= 40' x [3.14 x 100]/4
= 40x 78.5 = 3140 ft3 |
| Vol
= Space volume (ft3) |
|
|
C2=
200 ppm x e(-800 ft3/min x 20
mins/3,140 ft3) |
| Answer:C2=
1.2ppm |
|
Localized
Exhaust Ventilation
Dilution
ventilation is seldom effective in controlling
fume and dust-generating processes. However,
localized exhaust ventilation is better suited
to capture contaminants at or near their point
of generation using hoods or enclosures with
duct work connected to an exhaust fan. The contaminated
air is discharged outside the confined space,
thereby preventing its release into the employees'
breathing zones. This type of capture control
is especially effective for welding, cutting,
burning and brazing operations. The ventilation
system should maintain and exhaust airflow velocity
of at least 100 linear feet per minute in the
capture zone. Capture velocities decrease significantly
as the distance between the exhaust hood inlet
and welding source is increased. A good rule
is to keep the exhaust inlet within six to eight
inches of the source.
Some
operations may require both mechanical dilution
and localized exhaust ventilation to adequately
control contaminants in permit spaces. Ventilation
must be continuous during the entire length
of the entry operation to ensure that the ventilation
remains adequate and atmospheric hazards do
not develop. Frequent or continuous testing
must be performed for the entire length of the
entry operation to ensure that the ventilation
remains adequate and atmospheric hazards do
not develop.
Choosing
the most efficient ventilation system will depend
on careful evaluation of the permit space. Some
factors to consider in this evaluation process
include:
-
The fan or blower capacity.
-
The configuration and size of the space.
-
The number and size of the openings.
-
The airborne contaminant, its properties,
and its point of generation.
-
Positioning the blower or exhaust fan so that
there are no unnecessary bends in the hose.
A 90 degree bend or two can reduce efficiency
significantly.
-
Increasing the length of hose will increase
the friction and decrease the efficiency.
-
Make sure the ventilation system does not
block the exit if only one exit is available.
Make sure the authorized entrants can quickly
evacuate the space.
Cleaning
and Purging of Permit Spaces
Residues
of hazardous chemicals or materials capable
of decomposing (e.g., food products) must be
cleaned from the permit space to the extent
feasible prior to allowing entry. Pre‑entry
cleaning and purging are necessary because even
small amounts of some remaining materials can
create hazardous atmospheres. Some basic steps
to pre‑entry cleaning include:
-
First ensure that all material feed lines
and equipment are completely and effectively
isolated from the confined space.
-
Drain or pump out contents and remove as much
residue as feasible
-
Test for hazardous atmosphere. If the test
indicated harmful gases, vapors or mists,
the space must be purged and ventilated.
-
The particular purging agent used will depend
on such things as: the product in the permit
space and how it might react with the purging
agent; the work to be performed in the space;
and the suspected hazards.
-
To remove flammable atmospheres, it may be
necessary to purge the space with an inerting
gas such as nitrogen, carbon dioxide, argon,
etc. Other times, it may be possible to open
the space to allow air to naturally ventilate
the space.
-
Flammable and toxic residues on the walls
and floor should also be removed prior to
entry. Water is commonly used. If the residue
can not be washed away, steam may be used.
However, be aware that steam may not be suitable
for use in some situations where the substance
has a low ignition temperature or flash point.
This is because the steam condensate could
build up a static electric charge and create
a spark, thereby igniting the flammable atmosphere.
In situations where steam is needed to clean
or purge a vessel, make sure that the static
electricity is eliminated by bonding and grounding
the steam lines and vessel. Also, allow plenty
of time for the space to cool down after steam
is used.
-
Occasionally, cleaning solvents may be needed.
In these circumstances, make sure that the
cleaning compound is compatible with the residue
to be cleaned from the space.
-
Never assume that the space is safe for entry
after the purging and cleaning process is
completed. The atmosphere in the space must
be tested prior to entry. If a hazardous atmosphere
still exists or potentially exists, purge
and clean the space again.
-
Continue to ventilate the space and conduct
atmospheric testing frequently or continuously
during the entire entry procedure.
-
In the situations where the purpose of entry
is to clean the confined space, the space
must first be cleaned to the extent possible
from the outside. Proper personal protective
equipment must be used to protect individuals
from any hazards which might remain after
the pre‑entry cleaning. If atmospheric
hazards cannot be brought to acceptable levels
by purging, cleaning and continuous ventilation,
then special procedures must be put in place
after properly evaluating the situation. If
it is determined that an individual must enter
the permit space, then these special precautions
will include respiratory protection such as
an airline respirator with escape bottle of
Self‑Contained Breathing Apparatus (SCBA).
Note, most companies only allow such types
of entries during emergency situations because
of the immediate dangers and risks.
Isolation
and Lockout/Tagout Procedures
Prior
to allowing personnel to enter into a permit
space, the space must be evaluated to determine
what energy sources or hazardous materials are
present or potentially present. Steps must be
taken to isolate the space to prevent injury
to entrants by disconnecting, releasing or restraining
all energy sources and/or hazardous chemical
materials. Energy sources may include mechanical,
electrical, pneumatic, hydraulic, thermal, radioactive
and the effects of gravity; chemical hazards
may include flammable, reactive, toxic, irritating,
corrosive or oxygen displacing gases and vapors.
Isolation
Procedures
Isolation
procedures for chemical or gas lines must be
instituted to eliminate potential hazards by
such methods as:
-
blanking and blinding,
-
double‑block and bleed,
-
line breaking or misalignment and,
-
lockout/tagout.
Blanking
and Blinding is the absolute closure of
a pipe, line or duct by the fastening of a solid
plate, that completely covers the bore hole,
in line with the system. This plate (such as
a spectacle blind or a skillet blind) should
be made of the same material as the line and
must be able to withstand the maximum pressure
exerted by the line. This method involves installing
a blank between flanges with a leak-proof gasket
at a point in the conducting line as close to
the confined space area as possible. The blank
or blind should be marked identifying its purpose.
Double
Block and Bleed is a method that uses a
three‑point system to prevent leakage
into the confined space, two closed valves and
an open drain or vent valve located in between.
Lockout or tagging the valves in their required
positions provides additional protection.
Line
Breaking is the intentional and physical
disconnection of a pipe, line or duct. Added
protection is obtained by misaligning or removing
a section of the pipe, line or duct. Lines where
potentially hazardous residues might remain
downstream from the disconnecting point should
be purged. Any disconnected line, blank or block
valve should be checked with an atmospheric
testing monitor to make sure it is not leaking.
Lockout/Tagout
The
standard recognizes that energized parts of
electrical equipment and mechanical equipment
pose a significant hazard in many permit spaces.
As such, circuit parts of electrical equipment
must be deenergized and locked out/tagged out
or both in accordance with 29 CFR 1910.333.
Mechanical equipment must be locked out/tagged
out or both in accordance with 29 CFR 1910.147
or guarded in accordance with Subpart O of the
General Industry Standard.
General
requirements for effective lockout/tagout programs
include the following terms:
-
Identify and implement specific procedures,
in writing, for the control of hazardous energy
including preparation for shutdown, equipment
isolation, lockout/tagout application, release
of stored energy and verification of isolation.
-
Use locks where equipment can be locked out
-
Ensure that new equipment or overhauled equipment
can accommodate locks.
-
Employ additional means to ensure safety when
tags rather than locks are used.
-
Institute procedures for release of lockout/tagout
including machine inspection, notification
and safe positioning of employees and removal
of the lockout/tagout device.
-
Obtain standardized locks and tags which indicate
the identity of the employee using them and
that are of sufficient quality, durability
and quantity to ensure their effectiveness
-
Require that each lockout/tagout device be
removed by the employee who applied the device
-
Train employees in the specific energy control
procedures with training reminders as part
of the annual inspection of the control procedures.
-
Adopt procedures to ensure safety when equipment
must be tested during servicing, when outside
contractors are working at the site, when
a multiple lockout is needed for a crew servicing
equipment and when shifts or personnel change.
Control
of Combustible/Explosive Dust
As
discussed previously, combustible dust may also
pose a hazard in permit spaces. In circumstances
where explosive dust concentrations may possibly
meet or exceed their lower flammability limit,
measures are required to control or eliminate
the hazard. The following measures are recommended
to provide a safe environment for the employees:
-
Housekeeping ‑ dust explosions commonly
occur in series. The initial explosion stirs
up more dust and this additional dust propagates
a secondary explosion. The interior surfaces
should be kept as clean as possible and accumulations
kept to a minimum.
-
All sources of ignition must be removed from
the permit space. All equipment must be in
compliance with the National Fire Protection
Association (NFPA) 70 -National Electrical
Code for hazardous locations.
-
Static electricity must be prevented from
accumulating by proper bonding and grounding
methods. The relative humidity should also
be maintained to approximately 40‑60%.
-
Ventilation may also be necessary to control
the airborne dust hazard where needed (see
Ventilation Control Section).
PERSONAL
PROTECTIVE EQUIPMENT
Permit
spaces may pose many types of potential hazards
for personnel required to enter or working nearby.
Various types of equipment may be necessary
to ensure the safety of these individuals. Proper
planning and evaluation will determine what
equipment is needed. Equipment which may generally
be required include:
HEAD
PROTECTION: Head injuries are caused by
falling objects or by bumping the head against
a fixed object. Head protection, in the form
of protective hats, must do two things ‑‑
resist penetration and absorb the shock of a
blow.
Selection
-Each type of class of head protectors is intended
to provide protection against specific hazardous
conditions. An understanding of these conditions
will help in selecting the right hat for the
particular situation. For industrial purposes,
three classes are recognized:
Class
A -general service, limited voltage protection;
Class
B -utility service, high‑voltage helmets;
and
Class
C -special service, no voltage protection.
EYE
AND FACE PROTECTION: Employers must provide
eye and face protection suitable for the work
to be performed and employees must use this
equipment.
Suitable
eye protectors must be provided where there
is a potential for eye injury from machines,
flying objects, glare, liquids, injurious radiation
or a combination of these. Protectors must meet
the following minimum requirements:
-
Provide adequate protection against the particular
hazards for which they are designed:
-
Be reasonably comfortable when worn under
the designated conditions:
-
Fit snugly without interfering with the movements
or vision of the wearer;
-
Be capable of being disinfected;
-
Be easily cleanable; and
-
Be kept clean and in good repair.
Where
employees are at risk of contact with corrosive
chemicals, an eyewash with at least 15 minutes
flushing capacity is required.
Design,
construction, testing and use of eye and face
protection must be in accordance with ANSI Z87.1-1989.
HEARING
PROTECTION: Exposure to high noise levels
can cause hearing loss. It may also create physical
and psychological stresses such as increased
blood pressure, abnormal secretion of hormones
and tensing of muscles.
The
extent of damage primarily depends on the intensity
of the noise and the duration of exposure. Short-term
exposure to noise can cause temporary hearing
loss. Permanent damage is generally gradual
and the result of prolonged exposure to high
noise levels. There is no cure for permanent
noise‑induced hearing loss, so prevention
is the key.
Control
measures must be instituted to prevent hearing
loss. When possible, noise should be reduced
or controlled by engineering controls. In situations
where engineering controls cannot be used, another
effective method is the use of hearing protection.
Hearing protection comes in many different types
such as formable premolded plugs, semi‑aural
or canal caps and earmuffs. Each type has advantages
and disadvantages, as well as different noise
reduction ratings (NRR). The protection used
should reduce the noise levels to at least 90
decibels (dB) , and 85 dB for those individuals
who have experienced a significant hearing threshold
shift. Under some conditions, such as when noise
levels exceed 100 dB, it is necessary to use
combinations of hearing protection to ensure
adequate protection.
When
employees are exposed to noise levels exceeding
85 decibels, OSHA requires that the exposed
individual be included in a hearing conservation
program. For more specific information on a
hearing conservation program, refer to 29 CFR
1910.95 -Occupational Noise Exposure.
Employees
must be properly trained in correct use, maintenance
and the limitations of the hearing protection
they use. Employees should be able to select
from a variety of hearing protection to ensure
that the equipment fits properly and is comfortable
to wear.
In
permit spaces, excessive noise can interfere
with communication between the authorized entrant
and attendant. In situations where excessive
noise exists and the entrant must wear hearing
protection, steps must be taken to ensure that
communication is maintained. The communication
method used must ensure that the entrant can
immediately respond to an attendant's order
to evacuate the space if a prohibited condition
or situation arises. The method used must also
enable the attendant to detect any behavioral
changes in the authorized entrant. In some entry
operations, tugging on a rope may be adequate
to ensure effective communication. In other
circumstances, an intrinsically safe electronic
communication system may be needed. Some electronic
communication systems have headsets which also
have a noise reduction rating assigned to them.
Intrinsically
safe American National Standards Institute (ANSI)
Type II Sound Level Meters (SLM) should be used
to determine employee noise exposure levels.
An SLM is a lightweight instrument for the measurement
of sound pressure levels in decibels (dB). At
a minimum, the device should measure on the
A‑weighted scale at the slow level response
setting. The instrument should be calibrated
in accordance with the manufacturer's instructions.
TORSO
PROTECTION: Many potential chemical and
physical hazards may threaten the torsos of
permit space entrants such as contact with chemicals,
temperature extremes, cuts and abrasions. Part
of any pre‑entry evaluation involves determining
the proper protective clothing to use to protect
workers from these hazards. Manufacturers provide
a large selection of protective clothing for
specific applications. General selection categories
include single use and reusable clothing for
particulate and chemical protection, full body
chemical splash protection suits, insulated
workwear and specially flame‑resistant
clothing.
ARM
AND HAND PROTECTION: Potential hazards to
the arms and hands of employees working in or
around confined spaces can result in such injuries
as absorption of chemicals, burns, cuts, and
electrical shock. There is a wide assortment
of gloves, hand pads, sleeves and wristlets
for protection from various hazardous situations.
The protective device should be selected to
fit the job.
The
following items should be considered when selecting
chemical protective gloves and clothing:
-
Choose gloves designed to protect against
the specific chemical of concern.
-
Keep in mind all chemicals will eventually
permeate through protective clothing.
-
Combinations of protection may be required
since no single protective material can protect
against all chemicals.
-
Chemicals absorbed by protective clothing
continue to permeate through the protective
material.
-
Consult with the chemical protective clothing
manufacturer to determine the appropriate
material for the specific chemical of concern.
Employers may also want to test the material
against the chemicals to be encountered to
ensure its integrity.
-
Certain occupations call for special protection.
For example, electricians need special protection
from shock and burns. Rubber is considered
the best material for insulating gloves and
sleeves. Rubber protective equipment for electrical
workers must conform to the requirements established
by ANSI.
FOOT
AND LEG PROTECTION: For protection of feet
and legs from falling or rolling objects, sharp
objects, molten metal, hot surfaces and wet
slippery surfaces, workers should use appropriate
footguards, safety shoes, or boots and leggings.
To be acceptable, safety footwear must meet
ANSI requirements.
RESPIRATORY
PROTECTION: OSHA standards require employers
to establish and maintain a respiratory protection
program whenever respirators are necessary to
protect the health of employees. Before discussing
the requirements of OSHA's respirator standard,
it will be useful to review the various types
of available respirators.
Respiratory
protective devices fall into three classes:
air‑purifying; atmosphere or air supplying;
and combination air‑purifying and air‑supplying
devices. A brief discussion of each follows:
Class
1. Air-Purifying Devices
The
air-purifying device cleanses the contaminated
atmosphere. Chemicals can be used to remove
specific gases and vapors and mechanical filters
can remove particulate matter. This type of
respirator is limited in its use to those environments
where the air contaminant level is within the
specified concentration limitation of the device.
These devices do not protect against oxygen
deficiency.
"Oxygen
deficiency" means that the concentration
of oxygen is below the percentage found in normal
air and atmosphere‑supplying respiratory
protection must be provided. It exists in atmospheres
where the percentage of oxygen by volume is
less than 19.5 percent oxygen.
The
various types of air-purifying devices include
mechanical-filter cartridge; chemical‑cartridge,
combination mechanical-filter/chemical-cartridge,
gas masks; and powered air-purifying respirators.
Mechanical-filter
respirators offer respiratory protection
against airborne particulate matter, including
dusts, mists, metal fumes and smokes, but do
not provide protection against gases or vapors.
Chemical-cartridge
respirators afford protection against low
concentrations of certain gases and vapors by
using various chemical filters to purify the
inhaled air. They differ from mechanical-filter
respirators in that they use cartridges containing
chemicals to remove harmful gases and vapors.
Combination
mechanical-filter/chemical‑cartridge respirators
use dust, mist or fume filters with a chemical
cartridge for dual or multiple chemical exposures.
Gas
masks afford respiratory protection against
certain gases, vapors, and particulate matter.
Gas masks are designed solely to remove specific
contaminants from the air; therefore, it is
essential that their use be restricted to atmospheres
which contain sufficient oxygen to support life.
Gas masks may be used for escape only from atmospheres
that are immediately dangerous to life or health
(IDLH), but never for entry into such environments.
"IDLH"
means an atmospheric concentration of any toxic,
corrosive or asphyxiate substance that poses
an immediate threat to life or would cause irreversible
or delayed adverse health effects or would interfere
with an individual's ability to escape from
a dangerous atmosphere.
Canisters
for gas masks are color‑coded according
to the contaminant against which they provide
protection. This information is included in
the standard.
Powered
air-purifying respirators protect against
particulate, gases and vapors. The air-purifying
element may be a filter, chemical cartridge,
combination filter and chemical cartridge, or
canister. The powered air-purifying respirator
uses a power source (usually a battery pack)
to operate a blower that passes air across the
air-powered air-purifying respirator. It usually
supplies air at positive pressure (relative
to atmospheric) so that any leakage is outward
from the facepiece. However, it is possible
at high work rates to create a negative pressure
in the facepiece, thereby increasing facepiece
leakage.
Class
2. Atmosphere- or Air-Supplying Devices
Atmosphere-
or air-supplying devices are the class of respirators
that provide a respirable atmosphere to the
wearer, independent of the ambient air. Atmosphere-supplying
respirators fall into three groups: supplied-air
respirators, self-contained breathing apparatus
(SCBA), and combination-SCBA and supplied‑air
respirators. A brief discussion of each follows:
Supplied-air
respirators. These devices deliver breathing
air through a supply hose connected to the wearer's
facepiece or enclosure. The air delivered must
be free of contaminants and must be from a source
located in clean air. The OSHA requirements
for compressed air used for breathing, including
monitoring for carbon monoxide, are listed in
1910.134(d). Supplied-air respirators should
only be used in nonIDLH atmospheres.
There
are three types of supplied-air respirators:
Type A, B and C. Type A supplied‑air respirators
are also known as hose masks with blower. Air
is supplied by a motor-driven or hand-operated
blower through a durable, large diameter hose.
Type B supplied‑air respirators are hose
masks as described above without a blower. The
wearer draws air through the hose by breathing.
Type C supplied-air respirators are commonly
referred to as air-line respirators. An air-line
respirator must be supplied with respirable
air conforming to Grade D Compressed Gas Association's
Standard CGA G7.1-73, Commodity Specification
for Air, 1973. This standard requires air to
have the oxygen content normally present in
the atmosphere, no more than 5 milligrams per
cubic meter (mg/M3) of condensed hydrocarbon
contamination, no more than 20 parts per million
(ppm) carbon monoxide, no pronounced odor and
a maximum of 1,000 ppm of carbon dioxide.
There
are three basic classes of airline respirators
--continuous-flow, demand-flow, and pressure-demand
flow.
Continuous
flow. A continuous-flow unit has a regulated
amount of air fed to the facepiece and is normally
used where there is an ample air supply such
as that provided by an air compressor.
Demand
flow. These air-line respirators deliver
air flow only during inhalation. Such respirators
are normally used when the air supply is restricted
to high‑pressure compressed air cylinders.
A suitable pressure regulator is required to
make sure that the air is reduced to the proper
pressure for breathing.
Pressure-demand
flow. For those conditions where the possible
inward leakage (caused by the negative pressure
during inhalation that is always present in
demand systems) is unacceptable and where there
cannot be the relatively high air consumption
of the continuous‑flow units, a pressure‑demand
air‑line respirator may be the best choice.
It provides a positive pressure during both
inhalation and exhalation.
Types
A, B, and C that are approved for abrasive blasting
are designated AE, BE, and CE respectively.
These respirators are equipped with additional
devices designed to protect the wearer's head
and neck against impact and abrasion from rebounding
abrasive material and with shielding to protect
the windows of facepieces, hoods and helmets.
Self‑contained
breathing apparatus (SCBA) provide complete
protection against toxic gases and an oxygen
deficiency. The wearer is independent of the
surrounding atmosphere because he or she is
breathing with a system that is portable and
admits no outside air. The oxygen or air supply
of the apparatus itself takes care of respiratory
requirements.
Self-contained
Breathing Apparatus
There
are two basic types of self-contained breathing
apparatus: closed-circuit and open-circuit.
In the closed -circuit apparatus, the exhalation
is rebreathed by the wearer after the carbon
dioxide has been effectively removed and a suitable
oxygen concentration restored from sources composed
of: compressed oxygen; or chemical oxygen; or
liquid‑oxygen. In the open‑circuit
apparatus, exhalation is vented to the atmosphere
and is not rebreathed. There are two types of
open-circuit SCBAs: demand and pressure-demand.
Combination-SCBA
and supplied-air respirators are air-line
respirators with an auxiliary self‑contained
air supply. An auxiliary SCBA is an independent
air supply that allows a person to evacuate
an area or enter such an area for a very short
period of time where a connection to an outside
air supply can be made. These devices are approved
for use in IDLH atmospheres. The auxiliary air
supply can be switched on in the event the primary
air supply fails to operate. This allows the
wearer to escape from the IDLH atmosphere. Combination
air-line respirators with auxiliary SCBA are
designed to operate in three modes: continuous-flow,
demand-flow, and pressure‑demand flow.
Class
3. Combination Air-purifying and Atmosphere‑Supplying
Devices
This
type of device is a combination of an air-line
respirator with an auxiliary air-purifying attachment,
which provides protection in the event the air
supply fails. These respirators are available
in either continuous-flow or pressure-demand
flow and are most often used with a high-efficiency
filter as the air purifying element. Use in
the filtering mode is allowed for escape
only. Because of the posititve-pressure
and escape provisions, these respirators have
been recommended for asbestos work.
A
summary of the classification of respiratory
protective devices follows:
1)
Air-Purifying Devices
a. Mechanical‑filter cartridge
b. Chemical-cartridge
c. Combination mechanical‑filter/chemical
cartridge
d. Gas masks
e. Powered air-purifying
2)
Atmosphere or Air Supplying Devices
a.
Supplied‑air
1. Type A and AE
2.
Type B and BE
3.
Type C and CE (Airline)
(a) Continuous-flow
(b) Demand-flow
(c) Pressure-demand flow
b.
Self-contained breathing apparatus (SCBA)
1.
Closed-circuit
2.
Open-circuit
(a)
Demand
(b)
Pressure‑demand
c.
Combination-SCBA and supplied‑air
1.
Continuous-flow
2.
Demand-flow
3.
Pressure-demand flow
3)
Combination Air‑purifying and Atmosphere
Supplying Devices
a.
Continuous‑flow
b.
Pressure‑demand flow
OSHA
requires employers to develop written standard
operating procedures for employees who wear
respiratory protection. This written program
must address each element specified in 29 CFR
1910.134 (b) which are briefly outlined below.
MINIMAL
ACCEPTABLE RESPIRATOR PROGRAM
Requirement
Standard
Written
Operating Procedures .134(b)(1), (e)(1) and
(e)(3)
Proper
Selection .134(b)(2), (c) and (e)(2)
Training
and Fitting .134(b)(3), (e)(5) and (e)(5)(i‑iii)
Cleaning
and Disinfecting .134(b)(5) and (f)(3)
Storage
.134(b)(6) and (f)(5)(i‑iii)
Inspection
and Maintenance .134(b)(7),(e)(4),(f)(2)(I‑v)
and (f)(4)
Work
Area Surveillance .134(b)(8)
Inspection/Evaluation
of Program .134(b)(9)
Medical
Examinations .134(b)(10)
Approved
Respirators .134(b)(11)
|
Note
to the Employer: Refer to the sample respiratory
protection program provided in Appendix
I.
|
Precautionary
Equipment
Once
an entrance cover is removed, the opening must
be promptly guarded by a railing, temporary
cover, temporary fences or other temporary barriers.
This is necessary to protect individuals from
falling into the space, to protect entrants
from having objects fall onto them or due to
vehicular hazards. Barricades and/or pylons
may also be used so long as they physically
block access to the work area. Additionally,
warning signs are recommended to warn unauthorized
individuals not to enter the area. This may
be accomplished with a warning sign reading
"Danger-Confined Space Entry
in Progress --No Unauthorized Entry".
Communication
and Communication Systems
A
reliable method must be in place for attendants
to monitor the activities of the authorized
entrants and for the entrants to keep attendants
informed of their status in the event the permit
space must be evacuated. The standard allows
any effective means to be used to accomplish
this objective. Types of communication methods
include;
1)
Battery operated, voice activated communication
systems.
2)
Continuous electronic monitoring equipment
such as televisions, cameras, etc.
3)
Battery hand‑operated communications
devices (e.g., two way radios).
4)
Body alarm devices may also be helpful where
communication between the entrant and attendant
is difficult. This type of device is designed
to sound an alarm if the wearer does not move
during a specified period of time.
5)
Continuous and uninterrupted voice contact.
6)
Visual observation from outside the space
by the attendant.
A
clearly understandable back-up system (line-jerk
signals) is suggested should the primary system
fail. Failure of the primary system is sufficient
cause for immediate evacuation of the permit
space. Therefore, special attention must be
given to ensure that the communication system
is working properly, and that a device is used
that has sufficient transmission range. Also,
ensure outside lines of communication have been
established to summon rescue services.
The
exact type and extent of communication required
will depend on the operation being performed
and the hazards within the space. For example,
work that can only be performed in an IDLH atmosphere
(because engineering controls are infeasible)
would necessitate the use of continuous contact
monitoring equipment. In contrast, authorized
entrants working in a permit space that pose
only mechanical hazards would need a communication
system that provides only periodic monitoring.
The desired system is one that alerts the entrant
of any situation where evacuation is needed
and the entrant can perform self-rescue. If
no means of communication is available, then
the entry should be prohibited.
Retrieval
Equipment
The
standard requires employers to provide, maintain
and ensure the use of protective equipment.
This includes equipment necessary to facilitate
both entry into and exit from a permit space.
Whenever possible, rescues should be performed
outside the confined space so rescuers are not
exposed to hazardous conditions. Proper retrieval
equipment generally needed for permit space
entries include:
1)
chest or full-body harness
2)
heavy-duty life line
3)
mechanical winches
4)
tripods
5)
wristlets
Winches
should be selfbraking to prevent free falls
and to hold personnel in place when raising
and lowering has stopped. Additionally, tripods
should have two winches; one for lowering, arresting
and retrieving an entrant and a second for tools.
By having two winches, the entrant would not
be tempted to disconnected himself/herself from
the lifeline.
A
wide variety of harnesses are available. Some
coveralls have been specially designed with
a builtin fullbody harness for easy donning.
In
deciding what type of retrieval equipment is
needed for a specific entry operation, an evaluation
of the permit space must be conducted with the
following conditions in mind: size and configuration
of the confined space; size and location of
the opening; any obstacles within the space;
whether or not a rescue of the entrant would
be vertical or horizontal; and potential hazards
within the space.
Retrieval
lines are very effective in assisting in the
safe removal of unconscious personnel from many
permit spaces. Therefore, each authorized entrant
must use a chest or full body harness, with
a retrieval line attached at the center of the
entrant's back near shoulder level, or above
the entrant's head.
Wristlets
may be used in lieu of chest or full body harness
if the employer can demonstrate the use of a
harness is not feasible or creates a greater
hazard. Wrist harnesses are used where the entrant
may need to be withdrawn through a small opening.
In
some situations, however, retrieval lines have
been known to pose an additional risk by creating
entanglement hazard. In these particular situations,
the use of retrieval lines may be inappropriate.
In such cases, the following guidelines are
provided to determine if retrieval lines are
appropriate:
1)
A permit space with obstructions or turns
that prevent pull on the retrieval line from
being transmitted to the entrant does not
require the use of a retrieval system.
2)
A permit space from which an employee being
rescued with the retrieval system would be
injured because of forceful contact with projections
in the space does not require the use of a
retrieval system.
3)
A permit space that was entered by an entrant
using an air supplied respirator does not
require the use of a retrieval system if the
retrieval line could not be controlled so
as to prevent entanglement hazards with the
air line.
In
circumstances where retrieval lines or harnesses
cannot be worn, an alternative method must be
in place should an entrant need assistance.
If an acceptable alternative method is not available,
then entry is prohibited. In all circumstance,
inspect retrieval equipment prior to use.
Portable
Power Tools
Portable
power tools are generally grouped according
to their power source such as electrical, pneumatic,
hydraulic, gasoline and power-actuated.
In
confined spaces, air-operated pneumatic power
tools are normally recommended to avoid the
hazards associated with using these other types
of portable tools. Compressors servicing any
pneumatic tools must be located outside the
confined space and not pose a hazard. Ensure
that all safety devices are in place such as
air line safety check valves, safety retainers,
etc., before using air powered tools. If portable
electrical tools must be used, the electrical
equipment must meet the requirements of Article
500 of the National Electric Code (NEC) for
the specific hazardous location. An effective
grounding system must be instituted, or ground
fault circuit |